Ceiling Radiation / Fire Dampers as described are installed to protect the penetrations in the ceiling membrane portions of Fire rated Floor / Ceiling or Roof / Ceiling assemblies, as a shield against fire and heat radiation. [ Printer Friendly Adobe PDF File ] [ Features ] [ Typical Specification ] [ Installation / Maintenance ] [ Back to Dampers ].. |
|
|
The Model 5691A Ceiling Radiation / Fire Damper is test proven for 2
hours in a 120/120/120/ Boral Fire Rated ceiling system, and certified
for 1 and 1.5 hour ceiling systems. The Damper capabilities MUST cover three important areas, Flame, Heat
and Smoke: a) Stop Flames and combustible materials from entering the duct above, and spreading though out the building b) Reduce Radiant Heat which could ignite materials above the fire rated ceiling, and, c) Reduce the transfer of Smoke and dangerous Hot Gases from the fire zone to the non-fire zone.
|
|
|
|
|
Openings in Ceiling required to have a FRL, shall be protected by a Bullock Model 5691 Ceiling Radiation/Fire Damper or approved equivalent. The Dampers shall be provided where shown on drawings and wherever required to meet local regulations and MUST comply with AS1682.1-1990, AS1668.1-1998, Section 3.5. Dampers shall be mounted in strict accordance with the manufacture's installation instructions, to comply with the Certificates of test furnished by the manufacturer. The damper construction must be in compliance with the tested prototype containing features as: High yield stainless steel spring(s), four blade locking for positive closure to achieve low air/smoke leakage. Dampers installed in return air or exhaust applications must be capable of operation, at airflow rates in excess of the actual design application. (NOTE: Model 5691 dampers have a certified closure rating of 18m/s). Radiant metal duct surface temperature directly above the damper to below150oC after 120mins exposure. Blades must easily be reset from the underside for testing and maintenance in accordance with AS1851.6-1997. For further information please contact your local representative. |
|
|
Specifications
subject to change without notice.
![]()