|


[ Printer
Friendly Adobe PDF File ]
1. INITIAL DAMPER TEST -
Before installing Damper into wall, check damper's closing operation.
This can be achieved by removing UL33 rated fusible link. Hold the
damper in a stable upright position, then using the link strap or the
"cricket bat", push the blade vertically to the top. This will
clear the blade over the two locking tabs. Pivot the blade back against
the stainless steel spring(s) to the fully open position, then let the
blade close and lock. Replace fusible link and close link strap.
2.
Ensure wall penetration is correct size. Penetration size for this type
of installation should be 10mm larger than width and height dimension.
As per AS1530 Test Number FSV0538.
3.
Remove flange screws and detach flanges from casing.
4.
Apply a 20mm bead of fire rated mastic to base of penetration. Apply a
6mm bead of fire rated mastic to both edge faces of plasterboard surface
(see illustration).
5.
Slide damper in wall penetration and apply a 5mm bead of fire rated
mastic into side gaps. Apply a 10mm x 5mm x 2 beads of fire rated mastic
in gap above damper (see illustration). NOTE: Dampers are clearly marked
with "AIRFLOW" direction and "TOP" of unit.
6.
Replace flanges with a bead of fire rated mastic around penetration
where angles seal against plasterboard. NOTE: Do not overtighen flange
screws.
7.
Repeat INITIAL DAMPER TEST as outlined in point #1.
8.
Connect ductwork to fire damper using fire rated mastic to fill
recess if using raw edge connection, or apply mastic to both surfaces of
the TDF flange connections. (Bolts must be of a low melting point
material.)
|