|

[ Printer
Friendly Adobe PDF File
]
1. INITIAL DAMPER TEST - Before
installing damper into the wall, check damper's closing operation. This
can be achieved by placing damper into its upright installation
position. By placing both hands on the drive shaft, open the damper
blades by rotating the drive shaft towards you. This action simulates
the override of the knee action blade locking / sealing system, which is
normally done by the approved actuator to suit. Reverse this sequence to
close and lock the blades. CAUTION: Do NOT disconnect the McCabe(TM)
link from its operator, or injuries could be sustained. (Models 5020-1
& 5010 only).
2.
Advise builder of penetration construction detail. Refer Drawings.
3.
Ensure that the wall penetration is the correct size. Opening should be
16mm larger on top of damper and 10mm larger on either side of damper.
4.
Remove flange bolts and detach flanges from damper casings.
5.
Apply a 5mm deep bead of fire rated mastic along bottom edge s between
damper and penetration. Place damper into wall and on top of this mastic
to seal base gap.
6. All fire dampers are clearly marked with a "TOP"
sticker to verify dampers orientation. Airflow direction for this model
damper is optional.
7.
Insert 27mm diameter IBS rod (cylindrical fire rated sponge) into the
16mm expansion gap on top of damper. Seal all edges with another 5mm
deep bead of fire rated mastic to close off all gaps.
8.
Seal all angles to plasterboard wall surface with fire rated mastic.
Replace flanges making sure damper is firmly fixed within the wall.
NOTE: Do not over-tighten flange bolts.
9.
Repeat Point #1. INITIAL DAMPER TEST.
10.
Connect Ductwork to fire damper using approved fire rated mastic to fill
recess if using raw edge connection, or apply mastic to both surfaces of
the TDF/TDC flange connections. NOTE: Bolts must be of low melting point
material.
11.
Mount actuator to operate damper as per consultants design
specifications.
|