|

[ Printer
Friendly Adobe PDF File
]
1. INITIAL DAMPER TEST -
Before installing Damper into slab, check damper's closing operation.
This can be achieved by placing damper into it's installation position. Hold
blade stack whilst removing UL33 rated fusible link. Holding the blade
stack even with both hands release blades to allow closure. After
viewing proper operation gather up blade and replace fusible link to its
original position.
2.
Ensure slab penetration is correct size. Opening should be 26mm larger
than nominal size in both width and height. Refer AS1682.2-1990 Appendix
'C'.
3.
Remove bottom Flanges and slide damper down into slab penetration. NOTE:
All dampers are clearly labelled with "TOP" and "AIRFLOW
DIRECTION" orientation labels, these must be adhered to.
4.
From underneath side of slab reattach bottom flanges sealing between
flanges and slab as shown on diagram with an approved fire rated mastic.
NOTE: When reattaching flanges, do not overtighten flange screw/bolts.
5.
From top of damper, remove the 2x opposing side flanges and pack the
expansion gap completely with an approved high temperature ceramic fibre
insulation. Replace flanges, sealing between the flanges and slab with
an approved fire rated mastic.
6.
Now that the damper is securely fixed and sealed within the slab repeat INITIAL DAMPER TEST as outlined in point #1.
7.
Connect ductwork to fire damper using fire resistant mastic to fill
recess if using raw edge connection, or apply mastic to both surfaces of
the TDF/TDC flange connections. (bolts must be of a low melting point
material.)
|