1. INITIAL DAMPER TEST -
Before installing Damper into slab, check damper's closing operation.
This can be achieved by placing damper into it's installation position. Hold
blade stack whilst removing UL33 rated fusible link. Holding the blade
stack even with both hands release blades to allow closure. After
viewing proper operation gather up blade and replace fusible link to its
original position.
2.
Ensure slab penetration is correct size. Opening should be 26mm larger
than nominal size in both width and height. Refer AS1682.2-1990 Appendix
'C'.
3.
Remove flange screws/bolts and detach flanges from damper casing.
4.
Slide damper complete with metal seal attached into penetration. Apply a
bead of fire rated mastic to slab where flanges meet concrete slab.
5.
Replace flanges making sure damper is fixed firmly within the slab.
NOTE: DO not overtighten flange screws/bolts.
6.
Repeat INITIAL DAMPER TEST as outlined in point #1.
7.
Connect ductwork to fire damper using fire resistant mastic to fill
recess if using raw edge connection, or apply mastic to both surfaces of
the TDF/TDC flange connections. (bolts must be of a low melting point
material.)
|