Bullock Model 3100 Non-Return Air Dampers or equivalent shall be installed where shown on the drawings to suit the engineers design specifications. The dampers materials shell be determined according to the systems proximity to aggressive atmospheres, or its active purpose (Note: Dampers must not be installed in the fans turbulent zone.) Blades shall pivot on zinc plated mild steel shafts or 316 stainless steel to suit aggressive atmospheres, and shall not exceed 750mm in width. Hard wearing nylon bushes shall be used to prevent blade seizure or for systems operating at elevated temperatures above 80
deg.C bronze bushes shall be used. Frame design shall be stage and rigid to reduce flex, materials being aluminium, galvanised steel or stainless steel at a minimum 1.6mm thick.
Dampers are designed to control airflows not to structurally support the systems ductwork. Hang ductwork to Australian Standards using approved hanging methods to AS4254.
For further information contact your local representative.